TITANUS
MICRO·SENS
®
Pipe
Design
MS_A_04-en-e
Data: 01/09
4 –
35
4.4
Power
Supply
When sizing the power supply, the signal-ready status of the danger
alarm equipment and the alarm case are considered. When the plant is in
the signal-ready status, the power supply must deliver the idling current
to the air sampling smoke detection systems and guarantee charging of
the stand-by accus in accordance with DIN VDE 0833, Part 1
P18F
19
PT
.
The following formulae apply in case of alarm:
Power calculation
In case of alarm the current is calculated by the following formula:
Room protection
.
,
.
.
,
)
(
max
y
powersuppl
area
max
quiescent
area
max
alarm
room
total
I
n
n
I
n
I
I
≤
−
+
⋅
=
Equipment protection
power
max.
quiescent
alarm
equipment
total
I
n
n
I
n
I
I
≤
−
+
⋅
=
)
(
The current for charging the accus is calculated by the following formula:
Charging
current
24
8
,
0
nominal
charging
K
I
⋅
≈
max.
y,
powersuppl
charging
quiescent
equipment
total
I
I
n
I
I
≤
+
⋅
=
,
I
total
=
total current of all connected air sampling systems [A]
I
power supply, max.
=
max. supply current of the power supply unit [A]
n
=
total number of all air sampling systems connected to a
power supply unit
n
max area
=
total number of all air sampling systems in the area with
the highest power consumption
I
alarm
=
alarm current of an air sampling system [A]
I
quiescent
=
quiescent current of an air sampling system [A]
K
nominal
=
nominal capacity of the accumulators [Ah]
I
charging
=
charging current of the accumulators (within 24 h 80% of
the nominal capacity) [A]
The higher figure of the total current calculated (
I
total
) is used to design
the power supply!
The power consumption of the TITANUS
MICRO·SENS
P
®
P
can be found in
Chapter 3, "Technical Data".
TP
19
PT
80% charging in 24 hours
INSTRUCTION
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......