Commissioning
TITANUS
MICRO·SENS
®
7
– 8
Data: 01/09
MS_A_07-en-e
7.4 Testing the detection unit and
alarm forwarding
Trigger the TITANUS
MICRO·SENS
®
and test the transmission route to
the FAS as follows:
1. Spray the test aerosol either into the first aspiration aperture or into
the TITANUS
MICRO·SENS
®
pipe system test adapter.
2. Proceed on the basis of the following table.
Check whether ...
If this is not the case ...
the alarm on the air sampling smoke de-
tection system is displayed.
1. check whether the display plate is
connected.
2. there is a fault in the air sampling
smoke detector.
3. change the detection unit.
the alarm is transmitted to the FAS and
notified on the associated line.
1. check the transmission routes.
If the
LOGIC·SENS
is set to “ON” in the “Settings” screen of the
diagnosis tool (see Chapter 5.3 "Settings"), then this must be set to
"OFF" for testing triggering the alarm with the test aerosol, in order to
speed up alarm assessment.
Note all test data in the test record.
INSTRUCTION
INSTRUCTION
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......