2.3.5 Air return for pressure differences and air pollution
Fig. 2.28: Principle of air return in the
TITANUS
MICRO·SENS
®
If the TITANUS
MICRO·SENS
®
and the pipe system are installed in two
areas P1 and P2 with different air pressures, the air drawn off has to be
returned to the pipe system pressure range (see
2H
Fig. 2.28). Returning the
air can also avoid air pollution (e.g. smells) in neighbouring rooms.
TITANUS
MICRO · SENS
®
Air return
Air sampling pipe
Fig. 2.29:
TITANUS
MICRO·SENS
®
with air return
The air return pipe is mounted in the conical pipe plug-in connection for
the TITANUS
MICRO·SENS
®
air return (see
3H
Fig. 2.29). As the air return
pipe sits perfectly in the air return pipe, a firm hold is guaranteed.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......