TITANUS
TITANUS
TITANUS
U-pipe system
Double-U-pipe system
I-pipe system
®
®
®
TITANUS
®
M-pipe system
Fig. 4.2: Pipe designs
Direction change
Angles and bends in the pipe system increase flow resistance. For that
reason, it is necessary to limit the number of them to the amount re-
quired.
It is preferable to use bends, since angles have a higher flow resistance.
Angles should therefore only be used where they are necessary due to
structural constraints.
Corresponds to a straight pipe length of
Angle
1.5m
Bend
0.3m
If the pipe system includes angles or bends, the maximum overall length
of the pipe system will be reduced.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......