Installation
TITANUS
MICRO·SENS
®
5
– 2
Data: 01/09
MS_A_05-en-e
5.2
Installation
site
5.2.1 Fitting the TITANUS MICRO·SENS
®
air sampling
smoke detector
When choosing the installation site, ensure that the notices can be easily
seen.
When choosing the installation site, ensure that it is not within a space
where doors open.
Air return
Aspiration pipe
Aspiration
from above
min. 10 cm distance
from other objects
Aspiration
from below
Aspiration pipe
Fig. 5.1: Installation of
TITANUS
MICRO·SENS
®
Aspiration
from above
Ensure that the air outlet from the aspirating smoke detector is not blocked.
Maintain a distance of
at least
10 cm between the air outlet from the TITA-
NUS
MICRO·SENS
®
and surrounding objects (e.g. wall).
INSTRUCTION
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......