IR Oil Mist/Smoke Detector

Features

•  Automatic Self Calibration
•  Range = 2-30 metres
•  Weatherproof to IP65
•  Certified Intrinsically Safe EEx ib IIB T5
•  Robust Design
•  Heavy Duty Mounting Bracket available
•  Independent beam blocked output
•  Cleaning status output
•  Dual automatic compensation

IR6003/7

The IR6003/7 Oil Mist/Smoke Detector 

has been specially designed to be highly 

sensitive to the presence of oil & kerosene 

mists or smoke particles in the path of the 

detector beam. 

The detector has been developed for use in enclosed 
oil rig well head areas, generator rooms and turbine 
enclosures. The detector automatically compensates for 
contamination of the detector lenses and signals when 
a point is reached where further deterioration cannot be 
tolerated and the lense requires cleaning.  

Two levels of alarm status are provided. A low level alarm 
and a high level alarm. There is also a beam blocked 
status provided in the event that the beam is interrupted. 
The detector is intended to be used together with our 
P-UIM 6005/2 which will provide the detector as volt-free 
contacts.

PSF330JC_Time_Saver_Mount.indd   1

27/08/2019   17:23:12

Summary of Contents for IR6003/7

Page 1: ...or beam The detector has been developed for use in enclosed oil rig well head areas generator rooms and turbine enclosures The detector automatically compensates for contamination of the detector lenses and signals when a point is reached where further deterioration cannot be tolerated and the lense requires cleaning Two levels of alarm status are provided A low level alarm and a high level alarm ...

Page 2: ... Block If the level of obscuration increases suddenly to a high level of loss a beam blocked status will be latched and if the level is maintained for 60 seconds Beam Blocked will be reported LED flashes ON for 2 seconds If the beam blocked level of obscuration clears for more than a few seconds during the 60 second period monitoring period the detector will return to its normal operating state Du...

Page 3: ...dicator is lit steady Now remove the obstruction from the detectors path 5 Initiate a short reset and check that the P UIM returns to the status detailed in step 1 6 Initiate a long reset with the beam path blocked and check that the detector indicates a Life Fault LED is lit steady The P UIM Life indicator is lit steady Now remove the obstruction for the detectors path 7 Initiate a long reset and...

Page 4: ...tection IP65 BASEEFA 9 Cert BAS 02 ATEX 2313X EEx ib IIB T5 SIRA Cert IECEx SIR 14 0009X II2 G Ex ib IIB T5 Gb Accesories Flying Lead 01 33 14 Reflector Type 1 01 33 05 Reflector Type 2 01 33 10 Reflector Type 3 01 33 11 P UIM 01 33 22 0 20 mA Adapter 01 33 22A Heavy Duty M B 01 33 24 U Bracket 01 33 12 IR Alignment Tool 01 33 21 IR Test Film 01 33 26 Detector Monitoring Characteristics Detector L...

Page 5: ...ted to mechanical and thermal stress or where it may be attacked by existing or foreseeable aggressive substances Number Name General Count Number Name General Count 1 Shell 150 19 Technip Mar 5 2 BP 250 20 Det tronics 30 3 How 50 21 HESS 4 4 Total 20 22 Debyl Ltd 6 5 BNFL 8 23 North Sea 50 6 Micropack 10 24 STAT Oil 15 7 Maersk 10 25 Dutch Navy 16 8 Silvertech 30 26 Prudhoe Bay 10 9 ICS 60 27 FPS...

Page 6: ...ut notice PSF303JC Issue 1 08 19 www johnsoncontrols co uk There are many other companies who integrate our oil mist detection equipment into there safety systems These can range from Heavy Industrial Areas e g Engine Rooms Hazardous Areas Warehouses Marine Applications Oil Rigs FSPO s e g Shell BONGA Turbines Hyraulic Power Units Plus many more PSF330JC_Time_Saver_Mount indd 6 27 08 2019 17 23 14...

Reviews: