Product Description
TITANUS
MICRO·SENS
®
1
– 2
Data: 01/09
MS_A_01-en-e
Plug and Play
Installation and commissioning of the TITANUS
MICRO·SENS
®
are
simple with the Plug & Play function.
The device base is pre-assembled on site. By pre-setting the detection
unit for standard applications, the TITANUS
MICRO·SENS
®
is operational
immediately after it is inserted in the device base.
Redundancy
ventilators
For maximum safety, the TITANUS
MICRO·SENS
®
can be fitted with
redundancy ventilators as an option. During operation of the device with
the redundancy ventilator, ROOM·IDENT is not possible.
Network capacity
Fitted with a network card, several TITANUS
MICRO·SENS
®
devices can
be linked together in an Ethernet network. From a central point the user
can, for example, via VisuLAN T
®
monitor the whole plant for smoke
levels, airflow values etc. In addition, the TITANUS
MICRO·SENS
®
can
be integrated via the so-called OPC server into existing hazard and build-
ing management systems.
Potential
free
contacts
The TITANUS
MICRO·SENS
®
has one potential free contact each for
alarm and fault. So the smoke detection system can be switched to col-
lective and addressable
0F
1
recording lines of any central fire alarm systems
(FAS). A relay card (optional) can be connected to the TITANUS
MICRO·SENS
®
in order to connect the potential-free contact for the pre-
alarm to a detector line of a CFDU.
Diagnostics
With the DIAG 3 diagnostics device, there is a system available for
commissioning, inspection and servicing which makes it possible to
configure the device quickly and easily and contain faults. For
diagnostics purposes events are stored in the TITANUS
MICRO·SENS
®
for 72 hours.
Designing
detection
points
The monitoring surfaces of the detection point type for the TITANUS
MICRO·SENS
®
are to be set to match the point-specific smoke alarms.
The detection points can thus be designed similar to point-specific smoke
alarms in accordance with the particular national regulations.
Patented
detection
points
Wagner’s
patented detection reducing films, clips and banderols make
assembly simple and comfortable and avoid whistling operational noises.
An even inflow of air through all the apertures is achieved with a stepped
aperture diameter. These are fitted with rapidly checkable identification.
Extensive
pipe accessories
Wagner’s extensive range of accessories makes it possible to use the
TITANUS
®
aspirating smoke detection system even under the most
difficult of conditions. Products from various types of air filter from
condensate traps to blow through devices raise the serviceable life under
extreme dusty, humid and excessively cold environmental conditions.
1
Via the address module of the particular FAS.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......