Commissioning
TITANUS
MICRO·SENS
®
7
– 14
Data: 01/09
MS_A_07-en-e
4. After initialising, close the 4.2 mm aspiration hole on the test pipe
with some sticky tape. After about 5 secs, the fault display on the
device must start to flash. After about 35 secs, the fault display on
the device must be permanently on. The device signals the fault
“Air flow too low (statistical evaluation)“. The air flow figure is about
–35 %.
5. Open the 4.2 mm aspiration hole again. After a few seconds, the
fault display on the TITANUS
MICRO·SENS
®
must stop flashing.
6. Open the 7.0 mm aspiration pipe on the test pipe. After about 5 secs
the fault display on the device must start to flash. After about
35 secs, the fault display on the device must be permanently on. The
device signals the fault “Air flow too high (statistical evaluation)“. The
air flow figure is about +85 %.
7. Close the 7.0 mm aspiration hole again. The fault display on the
TITANUS
MICRO·SENS
®
must stop flashing after a few seconds.
8. Remove the test pipe and re-connect the pipe system.
After function tests are completed, the original settings must be restored.
Commissioning the TITANUS
MICRO·SENS
®
is to be repeated from
Chapter 7.3 “Air Flow Sensor Adjustment“.
Connection
testing
Test whether ...
1. The pipe system is firmly connected to the TITANUS
MICRO·SENS
®
pipe
connection.
2. All pipe fittings are glued and the pipe system is sealed tight. For this, first
close all aspiration apertures (e.g. with insulating tape). Using a flow
measurement device, measure the air flow at the aperture for the air flow
return.
3. The correct aspiration reducing films have been stuck to the aspiration
apertures.
After the air flow sensor is adjusted (Chapter 7.3 "Air Flow Sensor
Adjustment ") no more changes should be made to the pipe system.
If changes are necessary later, the air flow sensor must be
adjusted again.
After function tests are completed, the device and the pipe system must
be re-commissioned from Chapter 7.3 "Air Flow Sensor Adjustment".
After commissioning is completed, the settings should be recorded using
the diagnosis tool and stored. A print-out of the settings should be filed
with the project documents for subsequent follow-up work.
INSTRUCTION
INSTRUCTION
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......