TITANUS
MICRO·SENS
®
Pipe
Design
MS_A_04-en-e
Data: 01/09
4 –
7
4.1.3 Air flow monitoring
EN 54-20 requires the recognition of a 20 percent change in the air flow
volume by the detector module’s air flow sensor system. The activating
threshold of the air flow sensor system has to be adjusted to
≤
20 % in
order to achieve this. It is recommended to conduct an air pressure-
dependent air flow compensation for both of these settings.
Any threshold desired may be set with systems which do not require EN
54-20 conformity.
Project planning for the air flow monitoring system in sampling pipes is
carried out while taking into consideration the respective national regula-
tions for each country.
Adjusting the
air flow sensitivity
The air flow sensor sensitivity must be adjusted to the application in
question. Breakage and stoppages must be detected reliability with low
susceptibility to malfunction.
The activating threshold and for this reason the sensitivity of the air flow
sensor is continuously adjustable from 10 – 50 %.
In conformity with
EN 54-20
Triggering threshold
10 %
20 %
40 %
50 %
Sensitivity Very
high
High
Medium
Low
It is recommended to always select the greatest possible level which is
permissible according to national standards.
Dynamic
air flow sensor system
The device’s air flow monitoring enables the system to detect both pipe
breakages outside the device and sudden obstruction in individual aspi-
ration apertures (e.g. in the event of sabotage to the pipe system). The
dynamic air flow sensor system has been activated via the diagnostics
software, the following modifications have to be regarded.
TIP
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......