TITANUS
MICRO·SENS
®
Commissioning
MS_A_07-en-e
Data: 01/09
7
– 5
7.3 Air flow sensor adjustment
Air flow initialising for the TITANUS
MICRO·SENS
®
is completed suc-
cessfully if a stable status for temperature and air flow is set for a pe-
riod of 2 minutes. The maximum duration is 2 hours.
Air flow initialising for the TITANUS
MICRO·SENS
®
is completed
successfully if for a period of 2 minutes the following status is set:
- the temperature oscillates by less than 0.1K and
- the air flow does not oscillate too much (temperature regulation) and
- the ventilator voltage can be set properly
- ventilator and ventilator power supply working normally
The maximum duration is 2 hours.
Air flow initialising is interrupted immediately if any of the following errors
occur:
- Temperature measurement defective
- Air flow measurement defective
- Ventilator control defective
Types of adjustment
z
Adjustment can be conducted independently of the current air pres-
sure. The restrictions for this kind of adjustment can be found in Chap-
ter 4.3 "Air Flow Monitoring".
z
The air flow sensor can be adjusted as a function of the current air
pressure.
In order to be able to assess the air flow sensor figure correctly during
maintenance work, record the type of adjustment in each case in the test
records.
7.3.1 Air Pressure-Independent Adjustment
Air pressure-independent adjustment for the TITANUS
MICRO·SENS
®
happens completely automatically each time the detection unit is inserted
into the device base and the Jumper X4 is changed or via the diagnosis
tool.
During the learning phase, the alarm detection is fully functional. During
this time the operating display flashes and there must be no air flow
influences. When initialising is completed, the operating display changes
to a permanent light and the air flow sensor has determined its ideal
value for the connected pipe system.
INSTRUCTION
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......