background image

1

CSFM

 4300 Series

Wireless Smoke Detector

 LED

Test/Silence button

Sounder vent

Optional temperature sensor

Figure 1 - Detector Features

DESCRIPTION

The Sentrol 4300 Series smoke detector requires a
Sentrol 4000 RF gateway receiver with Rev J or higher
software and a compatible control panel sold sepa-
rately.  To install the detector, you will need the
programming guide for the control panel.

Depending on the model, the detector provides the
following features:

CleanMe

 self-diagnostics monitors its own sensitiv-

ity and operational status.  If the detector drifts out of
the UL listed sensitivity range or fails internal diagnos-
tics, it extinguishes its LED and sends a trouble signal
to the control panel.

Detector/base lock discourages unauthorized removal
of the detector by requiring a screwdriver to remove
the detector from the base.

Optional base tamper sends a trouble signal to the
control panel when the detector is removed from its
mounting base.

Optional mercury-tilt tamper

 

sends a trouble signal

to the control panel when the detector is not upside
down and/or horizontal.  Used for installations on
removeable ceiling panels

Optional integrated fixed 135°F temperature and
rate of rise heat detector
 trips an alarm based on
temperature detected.

Optional low temperature supervision sends a low
temperature signal when the ambient temperature
around the detector reaches approximately 43

°

F (6

°

C).

A separate transmitter signal (secondary address) is
assigned to a Critical Condition Monitoring(CCM) zon

e.

TRANSMITTED SIGNAL OUTPUTS

Depending on the model, the detector transmits the
following signals to the control panel:

• Alarm
• Alarm restore
• Tamper
• Low battery

SELECTING A LOCATION
S

electing a suitable location is critical to the operation

of smoke detectors.  This equipment should be installed
in accordance with the National Fire Protection
Association’s (NFPA) Standard 72.  See Figure 2.

A-8-1.2.1.C

   

Are  More  Smoke  Detectors  Desirable?

The required number of smoke detectors might not

provide reliable early warning protection for those areas

separated by a door from the areas protected by the

required smoke detectors. For this reason, it is recom-

mended that the householder consider the use of

additional smoke detectors for those areas for in-

creased protection. The additional areas include the

basement, bedrooms, dining room, furnace room, utility

room, and hallways not protected by the required

smoke alarms. The installation of smoke detectors in

kitchens, attics (finished or unfinished), or garages is

not normally recommended, as these locations occa-

sionally experience conditions that can result in im-

proper operation.

Important:

 Regulations pertaining to smoke detector

installations vary from state to state.  For more infor-

mation, contact your local fire department or local

authority having jurisdiction.

U

L

LISTED

U

N

D

E

R

W

R

IT

ER

S

LABORATOR

IE

S

O

F

C

A

N

A

D

A

LIS

TED BY

Figure 2 - Detector Placement

Wireless

sentrol

 4300 Series

Wireless Smoke Detector

U

L

LISTED

• CleanMe

• Maintenance alert
• Supervisory
• Low temperature supervison

TV Room

Dining
Room

Kitchen Bedroom

Bedroom

Bedroom

Living Room

= Required smoke detectors

Dining 

Room

Basement

Bedroom

Bedroom

Living 

Room

= Additional smoke detectors required for new construction

Summary of Contents for 4300 Series

Page 1: ...ED SIGNAL OUTPUTS Depending on the model the detector transmits the following signals to the control panel Alarm Alarm restore Tamper Low battery SELECTING A LOCATION Selecting a suitable location is critical to the operation of smoke detectors This equipment should be installed in accordance with the National Fire Protection Association s NFPA Standard 72 See Figure 2 A 8 1 2 1 C Are More Smoke D...

Page 2: ...See the control panel programming guide 6 Remove the red plastic dust cover from the detector The detector is shipped with a dust cover for protec tion on construction sites with dusty environments 7 Disconnect the alarm notification appliances service release devices and extinguishing systems and test the communication between the control panel and each smoke detector before permanently mounting ...

Page 3: ... of the mounting base To remove the detector from the mounting base when the detector base lock is used insert a small screwdriver into the locking tab slot on the side of the base and press in while simultaneously turning the detector counterclockwise 15 degrees See Figure 5 TESTING THE DETECTOR SENSITIVITY The 4300 Series provides a sensitivity level test mode that allows you to check the detect...

Page 4: ...en necessary clean the detector interior and replace the smoke chamber as follows 1 Disconnect the alarm notification appliances service release devices and extinguishing systems 2 Remove the detector from its mounting base See Attaching and Removing the Detector 3 Remove the batteries See Replacing the Batteries 4 Slide a flat blade screwdriver in the slot on the detector cap and gently push the ...

Page 5: ...st that everyone meet there during an alarm This will eliminate the tragedy of someone reenter ing the house for a missing member who is actually safe If you have children and or physically challenged people residing in your household use window decals to help emergency personnel identify the sleeping quarters of these individuals LIMITED WARRANTY Sentrol is a brand name of SLC Technologies Inc Th...

Page 6: ...moke detectors are very reliable but may not work under all conditions No fire detector provides total protection of life or property Smoke detectors are not a substitute for life insurance Smoke detectors require a source of power to work This smoke detector will not operate and the alarm will not sound if batteries are dead or not installed properly Unreliable transmission or receiving of radio ...

Page 7: ...7 ...

Page 8: ...ncoded Signal types Primary address alarm restore tamper low battery trouble maint CleanMe 1 hour supervisory Secondary address L models alarm restore Listings 4310 Series UL 217 CSFM 4330 Series UL 268 CSFM Approvals FCC IC l e d o M n o i t p i r c s e D S 0 1 3 4 d e t s i L 7 1 2 L U r e d n u o s B d 5 8 s e i r e t t a b m u i h t i l V 3 o w t r o t c e t e d e k o m s s s e l e r i w l o r...

Reviews: