Pipe Design
TITANUS
MICRO·SENS
®
4 –
14
Data: 01/09
MS_A_04-en-e
Procedure
In the following example, a project plan is supposed to fulfil class B re-
quirements with air filters LF-AD-1, with 4 apertures and without further
accessory. The red arrows show the possible project plans with varying
pipe shapes and fan voltages.
Selection
Selection of the corresponding project planning table based on the air filter to be
used (see Chap. 4.2.2 )
Result
1.
The project planning table has been determined
Selection
Selection of the number of aspiration apertures in the project planning table
Result
2.
The achievable sensitivity class for the selected number of apertures has been
determined
Selection
Determinations on the sensitivity necessary to achieve the sensitivity class
Result
3.
Determination of the detection unit and sensitivity setting
Selection
Selection of other pipe components ( e.g. steam trap see Chap. 4.2.2 described
components)
Result
4.
The project planning table has been determined
Selection
Pipe length selection
Result
5.
Determination of the pipe shape and necessary fan voltage.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......