
Pipe Design
TITANUS
MICRO·SENS
®
4 –
30
Data: 01/09
MS_A_04-en-e
4.3.2.4 Double-U-pipe
system
1 Pipe system
TITANUS
MICRO·SENS
P
®
P
d
TI
T
ANUS
M
ICR
O
·S
E
N
S
®
E
D
C
B
A
10
9
8
7
6
5
4
3
2
1
TITANUS
®
Fig. 4.13: Double U-pipe system, e.g. for equipment protection
Limit values
min. distance
TITANUS
P
®
P
– last T piece
2 m
max. distance
TITANUS
P
®
P
– last T piece
20 m
max. branch length
12,5 m
max. overall pipe length per pipe system
Pipe
∅
25 mm plus
pipe
∅
12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system with a ventila-
tor voltage of <10.5 V
Pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
8 x 3 m
max. number aspiration apertures (n) per pipe system
8 no.
minimum distance between the aspiration apertures (d)
0,1 m
maximum distance between the aspiration apertures (d)
4 m
Aspiration apertures
Number of apertures
per pipe system
4 8
∅
of all aspiration aper-
tures in mm
TP17F
18
PT
)
4,4
3,0
TP
18
PT
Opening diameter of the aspiration reduction film
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......