TITANUS
MICRO·SENS
®
Pipe
Design
MS_A_04-en-e
Data: 01/09
4 –
21
4.3.1.2 U-Pipe
system
1 Pipe system
TITANUS
MICRO·SENS
P
®
P
A
B
C
D
TITANUS
®
d
Fig. 4.6: U-Pipe system for area protection
Limit values
min. distance TITANUS
P
®
P
– T piece
2 m
max. distance TITANUS
P
®
P
– T piece
20 m
max. branch length
25 m
max. overall pipe length per pipe system
pipe
∅
25 mm plus
pipe
∅
12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system with a ventila-
tor voltage of <10.5 V
pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
8 x 3m
min. distance between 2 aspiration apertures (d)
4 m
max. distance between 2 aspiration apertures (d)
10 m
max. number aspiration apertures (n) per pipe system
8 no.
Aspiration apertures
Number of apertures
per pipe system
2 4 6 8
∅
Aspiration aperture in
mm
TP6F
7
PT
)
A
B
C
D
6,0
—
—
—
4,2
4,4
—
—
3,4
3,6
3,6
—
3,0
3,0
3,2
3,2
TP
7
PT
Opening diameter of the aspiration reduction film
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......