Installation
MS_A_05-en-e
Data: 01/09
5
– 25
5.10 Parallel
displays
5.10.1 Connecting the parallel displays to
TITANUS MICRO·SENS
®
Device base unit
1
4
Fig. 5.23: Connection of parallel display to
TITANUS
MICRO·SENS
®
To connect the parallel display, take the following steps:
n
Using a screwdriver loosen the four screws on the TITANUS
MICRO·SENS
®
detection unit.
o
Feed the fire alarm cable through the cable entry on the
TITANUS
MICRO·SENS
®
device base unit.
p
Feed the wires to the terminal block on the base unit according to
the switching plan (see Fig. 5.25).
q
Refit the detection unit by using a screwdriver to screw the four
screws on the detection unit of the device cover down firmly
.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......