Pipe Design
TITANUS
MICRO·SENS
®
4 –
34
Data: 01/09
MS_A_04-en-e
Arrangement
The aspiration apertures are to be arranged against the air flow.
Take care in the design that, for assembling the pipe system, the air
conditioning ducts are often only accessible from two sides.
Example
The following figure shows two design examples of pipe systems in air
conditioning ducts.
100
100
150
200
a
a
b
b
1/
2
b
1/
2 b
Duct cross-section: surface area A > 0.5 m²
Duct cross-section: surface area A 0.5 m²
≤
Fig. 4.15: Ducts with small and large duct cross-section