Testing record for Aspirating Smoke Detection System of the TITANUS MICRO · SENS
®
type
Device number
Detection unit serial number
Device base serial number
Commissioning
Visual check
(
9
/ –)
Low pressure
[Pa]
Sensitivity
[%/m]
Alarm delay
[s]
Air flow range
[10-50%]
Fault delay
[min]
Fault storing
(ja/nein)
Dynamic air flow
(ja/nein)
Location
(ja/nein)
LOGIC
· SENS
(ja/nein)
Air pressure-dependent adjustment
(ja/nein)
Air pressure-independent adjustment
(ja/nein)
Height
[m ü. NN.]
Air pressure
[hPa]
Ventilator voltage
[9-13,5V]
Air flow range
[m/s]
Temperature
[°C]
Blockage Fault
LED flashing
(
9
/ –)
Relay drops out after delay time
(
9
/ –)
Signal forwarding to fire alarm system
(
9
/ –)
Cause removed, LED out
(
9
/ –)
Relay picks up after threshold undercut
(
9
/ –)
Cause removed, LED stored
(
9
/ –)
Relay remains down for at least 100 secs
(
9
/ –)
Break Fault
LED flashing
(
9
/ –)
Relay drops out after delay time
(
9
/ –)
Signal forwarding to the FAS
(
9
/ –)
Cause removed, LED out
(
9
/ –)
Relay picks up after threshold undercut
(
9
/ –)
Cause removed, LED stored
(
9
/ –)
Relay remains down for at least 100 secs
(
9
/ –)
Main Alarm
LED flashing
(
9
/ –)
Relay picks up after delay time
(
9
/ –)
Signal forwarding to FAS
(
9
/ –)
LED stored
(
9
/ –)
Relay stored
(
9
/ –)
Location (ROOM-IDENT)
Free blow time
[10-255s]
Free blow ventilator
[9-13,5V]
Aspiration ventilator
[9-13,5V]
LED Location long-term aspiration aperture A
(yes/no) / [s]
LED Location long-term aspiration aperture B
(yes/no) / [s]
LED Location long-term aspiration aperture C
(yes/no) / [s]
LED Location long-term aspiration aperture D
(yes/no) / [s]
LED Location long-term aspiration aperture E
(yes/no) / [s]
Reaction Indicator
Aspiration aperture A
(yes/no)
Aspiration aperture B
(yes/no)
Aspiration aperture C
(yes/no)
Aspiration aperture D
(yes/no)
Aspiration aperture E
(yes/no)
Issuer: ……………………………
Signature: …………………………………
Key:
9
O.K.
– not O.K.
Measure/ +
Setting
Measure/ +
Setting
Measure/ +
Setting
Measure / +
Setting
Measure/ +
setting
Measure/ +
Setting
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......