Technical Description
TITANUS
MICRO·SENS
®
2
– 4
Data: 01/09
MS_A_02-a-en-e
steps of 0.1 %/m. The alarm is shown on the device via the alarm display
and forwarded to a connected fire alarm system (FAS).
By changing the delay time with the diagnosis tool, the forwarding of
alarms and faults can be set.
The intelligent
LOGIC·SENS
signal processing device serves to blank out
fire-like false alarms and ensures high false alarm safety
.
Airflow monitoring
An airflow sensor checks the connected pipe system for breaks and
blockages.
Depending on the design of the pipe system and the setting on the air-
flow sensor, the blockage of just one aspiration aperture can be picked
up. The airflow monitoring is
temperature-compensated
and can be
made
air pressure-dependent
.
At the end of the adjustable delay time, the fault is shown on the smoke
detection system and a corresponding message is forwarded to the
central fire alarm point via a contact. The monitoring windows can be
adjusted to the environmental conditions.
The principle of the airflow sensor signalling process can be seen in
0H
Fig.
2.6 .
Device
monitoring
The detection unit is monitored for dirt and signal fault. Any fault which
occurs is displayed at the TITANUS
MICRO·SENS
®
and can be for-
warded to the FAS via a contact.
Signal from the air flow sensor
Monitoring
window
Time
Blockage
Break
Airflow too high
Delay time
Fault message
Airflow normal
Airflow
too low
Fig. 2.6: Example signal pattern in the airflow sensor during faults
Airflow adjustment
Airflow adjustment on the TITANUS
MICRO·SENS
®
is fully automatic
when the detection unit is inserted in the device base, if previously the
Jumper X4 had been changed. This plug & play reduces the time needed
for commissioning to a minimum. It is also possible, however, to adjust
the airflow using the DIAG 3 diagnosis tool. This means the initialisation
phase can be carried out in an air pressure-dependent or air pressure-
independent manner.
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......