2.3.7 Steam trap for humid areas
TITANUS
®
steam trap
(max. 16 bar)
(optional)
45º elbow
45º elbow
Fig. 2.31: Steam trap to eliminate water vapour from the pipe system and to collect the con-
densate from the pipe system
If the TITANUS
MICRO·SENS
®
is operated in environments where
condensate can form in the pipe system, then a condensate trap is used.
To collect the condensate, the steam trap is fitted at the lowest point of
the pipe system, between the air filter and the smoke detection system.
Using 45° angles gives optimum wall distance.
The steam trap can be operated in a temperature range of 0°C to
+50°C. The sinter filter in the condensate trap has a pore width of 50
µm
and additionally absorbs coarse dust particles.
The condensate trap is used in the following areas:
Areas of application
Areas with severely oscillating temperatures and high air humidity
External areas
Sauna areas
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......