Pipe Design
TITANUS
MICRO·SENS
®
4 –
10
Data: 01/09
MS_A_04-en-e
4.1.5
Design
Limits
The following limit values must always be observed with the TITANUS
MICRO·SENS
P
®
P
:
•
The minimum pipe length between 2 aspiration apertures is
0.1 m
.
•
The minimum pipe length between 2 aspiration apertures when
locating a fire is
3 m
.
•
The maximum pipe length between 2 aspiration apertures is
10 m
.
•
The maximum monitoring surface area per aspiration aperture
corresponds to the monitoring area of a point-specific alarm
according to the regulations in the particular national standards.
•
Maximum 8 aspiration apertures are possible
TP0F
1
PT
.
•
Maximum 5 aspiration apertures are possible with site of a fire
location.
The maximum overall monitoring surface area for the TITANUS
MICRO·SENS
P
®
PP
P
and the maximum overall pipe length depend on the
design chosen.
max. overall monitoring surface area
per TITANUS MICRO · SENS
P
®
P
max. design pipe lengt
1F
2
PT
400 m²
Pipe
∅
25 mm: 50 m
plus
Pipe
∅
12 mm: 8 x 3 m
Because of country-specific regulations, there may be restrictions
compared to the design limits in the manual!
TP
1
PT
Designs / design forms not given in the manual are to be requested.
TP
2
PT
Depending on the design chosen, restricted values apply in part.
INSTRUCTION
Summary of Contents for TITANUS
Page 1: ...Technical Manual Air sampling smoke detection system TITANUS MICRO SENS ...
Page 2: ......
Page 4: ......
Page 10: ...TITANUS MICRO SENS Contents MS_A_Inhalt en e Data 01 09 ...
Page 14: ...General TITANUS MICRO SENS 0 4 Data 01 09 MS_A_00 en e ...
Page 44: ...Technical Description TITANUS MICRO SENS 2 24 Data 01 09 MS_A_02 b en e ...
Page 65: ...TITANUS MICRO SENS Pipe Design MS_A_04 en e Data 01 09 4 15 ...
Page 124: ...Installation TITANUS MICRO SENS 5 38 Data 01 09 MS_A_05 en e ...
Page 160: ...Commissioning TITANUS MICRO SENS 7 20 Data 01 09 MS_A_07 en e ...
Page 172: ......
Page 178: ......
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ......
Page 193: ......
Page 194: ......
Page 195: ......
Page 196: ......
Page 198: ......
Page 204: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e Data 01 09 ...
Page 206: ......
Page 208: ......