D200-72-00 

I56-1883-000

FTX-P1A Filtrex® Intelligent
Photoelectronic Smoke Detector

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

Before Installing

This detector must be installed in compliance with the con-

trol panel system installation manual. The installation must 

meet the requirements of the Authority Having Jurisdiction 

(AHJ).  Detectors  offer  maximum  performance  when 

installed in compliance with the CAN/ULC-S524. 

General Description

Filtrex®  uses  a  small  air  intake  fan  and  a  high  density 

replaceable filter. Air and smoke are drawn into a photo-

electric  sensing  chamber  while  airborne  particulate  and 

water mist are removed. The addressable-analog detector 

transmits an analog representation of smoke density over 

a  communication  line  to  a  control  panel.  Rotary-decade 

switches  are  provided  for  setting  the  sensor’s  address. 

Two  LEDs  on  the  sensor  are  controlled  by  the  panel  to 

indicate sensor status. 

Filtrex  smoke  detector  is  intended  for  use  in  normal 

environmental  conditions,  where  dust  and  other  air-

borne particulate are present at elevated levels. These 

elevated  levels  tend  to  cause  false  alarms  and  high 

maintenance in standard detectors. Filtrex provides a 

protective enclosure for a photoelectric smoke detec-

tor chamber and allows smoke detection in areas that 

tended to use exclusively heat detection.

Filtrex  requires  compatible  addressable  communica-

tions  to  function  properly.  Connect  this  detector  to 

listed-compatible control panels only.

Spacing

System  Sensor  recommends  spacing  detectors  in  com-

pliance  with  CAN/ULC-S524.  In  low  air  flow  applications 

with  smooth  ceilings,  space  detectors  30  feet  apart.  For 

specific information regarding sensor spacing, placement, 

and  special  applications,  refer  to  CAN/ULC-S524  or  the 

System Sensor 

Guide For Proper Use of System Smoke 

Detectors

,  available    from  System  Sensor  (P/N  I56-407-

XX).

WARNING

Filtrex  is 

not

  designed  to  operate  in  explosive 

environments.

Specifications 

Operating Voltage Range: 

15 to  32 VDC

Detector Current: 

230 

µ

A @ 24 VDC (without communication)

 

 

285 

µ

A @ 24 VDC (one communication every 5 sec. with LED enabled)

Auxiliary Power Supply Voltage:  15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.

Auxilary Power Supply Current – 

 

Peak: 

123 mA max.

 

Average: 

27 mA max.

Operating Humidity Range:  

10% to 93% Relative  

Humidity, noncondensing

Operating Temperature Range: 

0° to 50°C (32° to 122°F)

Height:    

2.8 inches (43 mm)

Diameter: 

6.1 inches (155 mm) installed in B501B-FTXA

Weight:    

7.3 oz. (207 g)

Compatibility: 

Backwards compatible with 200 and 500 series products’ protocol                                    

Mounting Base: 

Requires B501B-FTXA 

 

6581  Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

Summary of Contents for Filtrex FTX-P1A

Page 1: ...er and allows smoke detection in areas that tended to use exclusively heat detection Filtrex requires compatible addressable communica tions to function properly Connect this detector to listed compatible control panels only Spacing System Sensor recommends spacing detectors in com pliance with CAN ULC S524 In low air flow applications with smooth ceilings space detectors 30 feet apart For specifi...

Page 2: ... detector can sense smoke LISTED COMPATIBLE CONTROL PANEL AUX POWER SUPPLY A U X A U X A U X A U X 2 3 RA 4 S 1 1 2 3 RA 4 S Testing Before testing notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Disable the system to prevent unwanted alarms All detectors must be tested after installation and periodi cally thereafter Testing methods mu...

Page 3: ...led location it is recom mended that the following test program be conducted 1 Install Filtrex in the desired location 2 Connect Filtrex to the fire alarm control panel 3 Maintain a record for at least 90 days of any mainte nance performed on or required by Filtrex 4 At the end of the test period use the record to develop and schedule maintenance Filtrex detectors should be serviced at regular int...

Page 4: ...d filter was the cause of the trouble condition normal detector operation should resume automatically within five minutes If the trouble condition persists the detector must be returned for repair or replacement Installing Filtrex Into Base 1 Align the detector at a right angle to the base with the five wires and connector adjacent to the connector receptacle as shown in Figure 5 2 Plug the wired ...