Control unit for weather-compensated mode with Comfortrol prog. unit
Summary of coding addresses
(cont.)
Coding in the
as delivered
condition
Address:value
Function mode
Coding
change
Address:value
Possible change
Heating circuit pump
(cont.)
046:045
Heating circuit pump
speed in reduced
mode
046:001
to
046:100
*1
Lowest heating circuit
pump speed in reduced
mode
Highest heating circuit
pump speed in reduced
mode
Programming unit or remote control unit
009:000
Boiler water temp.
display
009:001
Display of outside temp.
019:000
Weather-compensated
mode (WS function)
for all connected
heating circuits
019:001
*2
H
For systems with one
heating circuit without
mixer
or
one heating circuit
with mixer:
Operation with room
temp. hook-up (RS
function)
H
For systems with one
heating circuit without
mixer
and
one heating circuit
with mixer:
Weather-compensated
mode (WS function)
for the heating circuit
without mixer and
operation with room
temp. hook-up (RS
function) for the
heating circuit with
mixer
*1
Each step represents approx. 20Ărpm
*2
This conversion is only appropriate if the programming unit is set into the wall
mounting fixture.
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...