43
Troubleshooting
Repairs
(cont.)
Checking the safety chain
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 90Ă
º
C:
H
Pull off one cable of thermo-
couplesĂ
A
.
H
Check thermocouple continuity
with a multimeter.
H
Remove faulty thermocouples.
H
Coat replacement thermocouples
with heat conducting paste and
install.
H
After commissioning, press reset
keyĂ"
EU
" on the control unit.
5692Ă485
G
B
A