87
Control unit for weather-compensated mode with Comfortrol prog. unit
Summary of coding addresses
(cont.)
Coding in the
as delivered
condition
Address:value
Function mode
Coding
change
Address:value
Possible change
Boiler
(cont.)
0C5:000
Signal external
demand activated:
see the following table
0C5:001
to
0C5:011
Signal external
demand activated:
see the following table
Modification options coding addressĂ0C5 "External demand"
Coding
Heating
circuit
Heating circuit with mixer
(extension kit)
Circulation
pump for
Boiler water
temperature
pump
Heating circuit
pump
Mixer
p
p
DHW cylinder
loading
0C5:000 ON
OFF
Closed
OFF
Will be
0C5:001 OFF
OFF
Closed
OFF
maintained
at the set
0C5:002 ×
OFF
Closed
OFF
at the set
value acc. to
0C5:003 OFF
×
×
OFF
value acc. to
coding
dd
0C5:004 ON
×
×
OFF
address
"0A2"
0C5:005 ×
×
×
OFF
"0A2"
0C5:006 OFF
OFF
Closed
×
0C5:007 ON
OFF
Closed
×
0C5:008 ×
OFF
Closed
×
0C5:009 OFF
×
×
×
0C5:010 ON
×
×
×
0C5:011 ×
×
×
×
× = in a normal control function
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...