Removing the burner and checking the burner gasket for leaks
1.
Switch off the system on the
control unit and the mains
electrical supply.
2.
Close the gas shut-off valve and
safeguard against re-opening.
3.
Pull the electrical cables off fan
motorĂ
A
, differential pressure
sensorĂ
B
, gas valveĂ
C
, ionisation
electrodeĂ
D
, ignition unitĂ
E
and
earthĂ
F
.
4.
Loosen gas connection pipeĂ
G
.
5.
Slacken six nutsĂ
H
and remove
the burner.
¨
Do not rest the burner on the
gauze assembly (wire mesh).
6.
Check the burner gasket for
damage (U-shaped gasket, see
parts list) and replace if necessary.
¨
Generally, replace the burner
gasket every two years.
5692Ă485