Control unit for weather-compensated mode with Comfortrol prog. unit
Adjusting heating curves
Please note:
Heating circuitĂA =ĂHeating circuit
without
mixer
Heating circuitĂB =ĂHeating circuit
with
mixer
Heating curve slope
After opening the programming unit
flap, follow the following menu path:
Menu item
Key
³
HEATING CIRCUITĂA "
A
"
or
HEATING CIRCUITĂB "
B
"
³
HEATING CURVE
"
B
"
³
CHANGE
"
A
"
Heating curve level
After opening the programming unit
flap, follow the following menu path:
³
HEATING CIRCUITĂA "
A
"
or
HEATING CIRCUITĂB "
B
"
³
HEATING CURVE
"
B
"
³
CHANGE
2Ă×Ă"
A
"
5692Ă485
G
B
110
Boiler water temperature or flow temperature in ăC
+20
-20
0.2
1.4
3.5
Outside temperature in
º
C
º
110
-13
Boiler water temperature or flow temperature in ăC
+20
-20
1.4
+40
Outside temperature in
º
C
º