Control unit for weather-compensated mode with Comfortrol prog. unit
Summary of coding addresses
(cont.)
Coding in the
as delivered
condition
Address:value
Function mode
Coding
change
Address:value
Possible change
DHW cylinder
(cont.)
007:000
Setting range for DHW
temp. 10 to 60Ă
º
C
007:001
Setting range for DHW
temp. 10 to 70Ă
º
C
Warning
Observe max.
permissible DHW
cylinder water temp.
017:001
The circulation pump
starts immediately
017:000
The circulation pump
will be switched on
subject to the boiler
temp.
018:000
Circulation pump with
run-on
018:001
Circulation pump
without run-on
028:000
During DHW heating,
the boiler water temp.
is a max. of 20ĂK higher
than the set DHW
cylinder temp.
028:001
During DHW heating,
the boiler water temp.
is limited by the high
limit thermostat to
78Ă
º
C.
047:_
Ă
_
Ă
_
Actual temp. at the
DHW cylinder temp.
sensorĂ
$
in
º
C (no
adjustment possible)
0A0:020
*1
Differential temp.
between the set boiler
water temp. and the set
DHW cylinder temp.
during DHW heating
0A0:010
to
0A0:050
Differential temp.
setting range
10 to 50Ă
º
C
0A7:060
Set value of the
"Auxiliary function for
DHW heating" (DHW
heats quickly to 60Ă
º
C)
0A7:061
to
0A7:070
Setting range between
61 and 70Ă
º
C
*1
Only effective with codingĂ028:000.
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...