Control unit for weather-compensated mode with Comfortrol prog. unit
Summary of coding addresses
(cont.)
Coding in the
as delivered
condition
Address:value
Function mode
Coding
change
Address:value
Possible change
Boiler
(cont.)
0A8:000
Signal external
blocking enabled:
see the following table
0A8:001
to
0A8:007
Signal external
blocking enabled:
see the following table
Modification options ć coding addressĂ0A8 "External blocking"
Coding
Heating
circuit
Heating circuit with mixer
(extension kit)
Circulation
pump for
Burner
pump
Heating circuit
pump
Mixer
p
p
DHW cylinder
loading
0A8:000 ×
×
×
×
Blocked
0A8:001 OFF
OFF
Closed
OFF
Blocked
0A8:002 ×
×
×
OFF
Blocked
0A8:003 ×
OFF
Closed
×
Blocked
0A8:004 OFF
×
×
×
Blocked
0A8:005 OFF
×
×
OFF
Blocked
0A8:006 OFF
×
×
×
Blocked
0A8:007 OFF
OFF
Closed
×
Blocked
× = in a normal control function