90
Control unit for weather-compensated mode with Comfortrol prog. unit
Summary of coding addresses
(cont.)
Coding in the
as delivered
condition
Address:value
Function mode
Coding
change
Address:value
Possible change
Heating circuit pump
005:001
With heating circuit
pump logic function
005:000
Without heating circuit
pump logic function
006:001
Heating circuit pump
speed for reduced
mode acc. to coding
addressĂ"044:_
Ă
_
Ă
_"
006:000
Heating circuit pump
speed for reduced
mode acc. to coding
addressĂ"046:_
Ă
_
Ă
_"
008:000
Heating circuit pump
"ON" for heating
system designs
"000:002" and "000:003"
(connection to
plugĂ"20
Ă
A")
008:001
Heating circuit
pumpĂ"OFF" for
heating system
designsĂ"000:002"
and "000:003"
013:001
With variable speed
heating circuit pump
(automatic recognition)
013:000
Stepped heating circuit
pump (e.g. transfer
mode for service)
044:020
Minimum heating
circuit pump speed
044:001
to
044:100
*1
Lowest value for the
lower heating circuit
pump speed (do not
set below "020")
Highest value for
lower heating circuit
pump speed
045:065
Highest heating circuit
pump speed
045:001
to
045:100
*1
Lowest value for upper
heating circuit pump
speed
Highest value for
upper heating circuit
pump speed
*1
Each step represents approx. 20Ărpm
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...