Control unit for weather-compensated mode with standard prog. unit
Summary coding levelĂ2
For a sequence of steps to call up coding levelĂ2, see pageĂ72.
Coding in the
as delivered
condition
Address:value
Function mode
Code
change
Address:value
Possible change
Boiler
038:040
Minimum flow temp. in
heating mode
038:020
to
038:127
042:075
Maximum boiler water
temp. in heating mode
042:020
to
042:127
Max. possible boiler
temperature 82Ă
º
C
102:075
Set boiler water
temperature for
external demand 75Ă
º
C
102:000
to
102:127
Setting range of the set
boiler water temp. 0 to
127Ă
º
C (max. possible
boiler water temp.
82Ă
º
C)
108:000
Signal external
blocking enabled: see
the following table
108:001
to
108:007
Signal external
blocking enabled: see
the following table
Modification types ć coding addressĂ108 "External blocking"
Coding
Heating
circuit
Heating circuit with mixer
(extension kit)
Circulation
pump for
Burner
pump
Heating circuit
pump
Mixer
p
p
DHW cylinder
loading
108:000
×
×
×
×
Blocked
108:001
OFF
OFF
Closed OFF
Blocked
108:002
×
×
×
OFF
Blocked
108:003
×
OFF
Closed ×
Blocked
108:004
OFF
×
×
×
Blocked
108:005
OFF
×
×
OFF
Blocked
108:006
OFF
×
×
×
Blocked
108:007
OFF
OFF
Closed ×
Blocked
× = in a normal control function
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...