Control unit for weather-compensated mode with standard prog. unit
Calling up coding levelĂ2
Please note:
For systems with wall mounting fixtures, the programming unit must be
plugged into the control unit, if coding is to be carried out at coding levelĂ2.
For a summary of the coding addresses of coding levelĂ2, see pageĂ73.
1. Call up coding levelĂ1
Simultaneously press the red
keyĂ"
w
" and the blue keyĂ"
M
".
Hold the keys down until after
approx. 5Ăseconds "01:00" is
displayed.
2. Call up coding levelĂ2
Simultaneously press the red
keyĂ"
p
" and the blue keyĂ"
r
".
Hold both keys down until after
approx. 5Ăsecs. (e.g. to "o:000").
3. Selecting the coding address
Press keyĂ"
u
" and turn the rotary
selectorĂ"
G
" clockwise, until
the required coding address is
displayed.
4. To change the coding address value
Press keyĂ"
1Ć7
" and turn the rotary
selectorĂ"
G
" until the required
value of the coding address appears.
5. Terminating coding
Press the red keyĂ"
r
".
5692Ă485
G
B
-
+
1-7
?
1 2 3 4 5 6 7
01:00