23
Initial start-up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Adjusting the heating system design
H
For selection of an appropriate design, see the following diagram.
H
Coding steps
ćĂwith standard programming unit, see pageĂ62,
ćĂwith Comfortrol programming unit, see pageĂ81.
Please note:
If there is no directly connected heating circuit without mixer, set the coding
address toĂ"22:01" (for standard programming unit) or "008:001" (for
Comfortrol programming unit).
Standard
programming
unit control
Comfortrol
programming unit
control
DesignĂ"04:01"
DesignĂ"000:001"
Heating system with
one heating circuit without mixer,
and with DHW heating.
M
M
or
Heating system with low loss header
and heating circuits downstream
with separate heating circuit control,
and with DHW heating.
The coding is automatically
adjusted during DHW cylinder
sensor connection when operating
with a DHW cylinder.
5692Ă485
G
B