Control unit for weather-compensated mode with standard prog. unit
Calling up coding levelĂ1
Please note:
For a summary of the coding addresses of coding levelĂ1, see pageĂ67.
1. Calling up the coding level
Simultaneously press red keyĂ"
w
"
and blue keyĂ"
M
".
Hold the keys down until after
approx. 5Ăseconds "01:00" is
displayed.
2. Coding address selection
Press keyĂ"
u
" and turn rotary
selectorĂ"
G
" clockwise, until
the required coding address is
displayed.
3. To change the coding address value
Press keyĂ"
1Ć7
" and turn rotary
selectorĂ"
G
" until the required
value appears.
4. Terminating coding
Press red keyĂ"
r
".
5692Ă485
G
B
-
+
1-7
?
1 2 3 4 5 6 7
01:00