19
Initial start-up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Cleaning the combustion chamber/heating surfaces and
installing the burner
1.
Clean combustion chamberĂ
A
and heating surfacesĂ
B
, if
required, with a brush, or flush
with water.
¨
Avoid scratching parts that are
in contact with flue gases.
Only use plastic brushes and
NOT wire brushes.
Apply a solvent-/potassium-free
cleaning agent where residues
remain:
H
Remove soot deposits with
alkaline cleaning agents with
additional surfactants
(e.g. FauchĂ600).
H
Remove coatings and surface
discolouration (yellowĆbrown)
with slightly acidic, chloride-free
cleaning agents based on
phosphoric acid
(e.
Ă
g. AntoxĂ75ĂE).
H
Flush thorougly with water.
Please note:
FauchĂ600 and AntoxĂ75ĂE are
supplied by
Hebro Chemie GmbH
Rostocker StraßeĂ40
DĆ41199ĂMönchengladbach
c
:
Intec BassersdorfĂAG
GrindelstrasseĂ12
Postfach
CHĆ8303ĂBassersdorf
2.
Install the burner and torque
diagonally to 4.5ĂNm.
3.
Secure the gas connection pipe
with a new gasket.
¨
ĂSafety instruction
Carry out a leak test.
4.
Connect the electrical leads to the
corresponding components.
5692Ă485
G
B
A
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...