55
Control unit for constant temperature mode
Changing parameters in service positionsĂ"S
Ă
1" to "S
Ă
7"
(cont.)
S
Ă
1Ăć Pump run-on time when using a clock thermostat
The clock thermostat input will only be evaluated in heating mode.
The boiler water temperature will be maintained and the circulation pump
remains switched ON, if the clock thermostat issues a heat demand.
The burner will be switched OFF without request.
You can set the run-on time for the circulation pump.
For setting steps, see pageĂ54.
Parameter
Circulation pump behaviour
0
OFF immediately after burner
switch-off
1 to 120
As delivered condition: "2"
As delivered condition:
(2Ămin run-on)
ă1 to 120
Ă
minutes run-on.
Setting step range:
ă1 to ă10Ăminutes in 1 min. steps,
15 to 120Ăminutes in 5 min. steps.
S
Ă
2Ăć External blocking
Subject to set parameters, different components are disabled when
contactĂ"X
Ă
6.1"
Ă
Ć
Ă
"X
Ă
6.2" closes.
Please note:
Change strapping plugĂ"X
Ă
6" on circuit boardĂVR
Ă
20 toă
For setting steps, see pageĂ54.
Parameter
Blocked-out components
0
Burner
1
Heating circuit and DHW heating
2
Heating circuit
3
Domestic hot water heating
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...