44
Troubleshooting
Repairs
(cont.)
Checking fuses
1.
Switch OFF the mains power.
2.
Flip down the control unit and
remove coversĂ
A
and
B
.
3.
Check fuseĂF
Ă
1, F
Ă
2 and F
Ă
3.
When replacing fuses, observe the
following:
F
Ă
1: 4ĂA (slow), 250ĂV
(max. dissipated energyĂ
x
Ă 1.6ĂW)
or
6.3ĂA (slow), 250ĂV
(max. dissipated energyĂ
x
Ă 2.5ĂW)
F
Ă
2: 2.5ĂA (slow), 250ĂV
(max. dissipated energyĂ
x
Ă 1ĂW)
F
Ă
3: 6.3ĂA (slow), 250ĂV
(max. dissipated energyĂ
x
Ă 2.5ĂW).
5692Ă485
G
B
A
F3
F1
F2
B