38
Troubleshooting
Repairs
Scanning the actual and set temperatures for
:
H
Control unit for constant temperature mode, see pageĂ59.
H
Control unit for weather-compensated mode with
ć standard programming unit, see pageĂ77,
ć Comfortrol programming unit, see pageĂ95.
Checking the outside temperature sensor
(control unit for weather-compensated mode)
1.
Pull plug-in connectorĂ"X
Ă
6" off the
control unit.
2.
Test the resistance across
terminals "X
Ă
6.3" and "X
Ă
6.4" on
the pulled connector and compare
with the curve.
3.
Where actual values strongly
deviate from the curve values,
disconnect the wires at the sensor
and repeat test directly at the
sensor.
4.
Depending on the result, replace
the cable or the outside
temperature sensor.
5692Ă485
G
B
-40 -30 -20 -10
0 +10 +20 +30
Outside temperature in
º
C
400
420
440
460
480
500
520
540
560
580
600
Resistance in
Ω