65
Control unit for weather-compensated mode with standard prog. unit
Adjusting heating curves
(cont.)
Heating curve level
DesignsĂ"04:00" and "04:01":
Heating circuit
without
mixer
DesignsĂ"04:02" and "04:03":
Heating circuit
with
mixer
Control unit setting:
Differential temperature
DesignsĂ"04:02" and "04:03"
Setting of coding addressĂ"07"
Setting range for differential temp. of
"07:00"Ă=Ă6ĂK to "07:15"Ă=Ă36ĂK
(Change per step: 2ĂK)
As delivered condition: "07:01"Ă=Ă8ĂK.
Please note:
If VitotronicĂ050 is connected, the set
differential temperatures add up (as
delivered condition respectively 8ĂK).
Therefore set the differential
temperature on VitotronicĂ050
appropriately lower.
5692Ă485
G
B
110
+20
-20
Outside temperature in
º
C
Outside temperature in
º
C
Boiler water temperature or flow temperature in ăC
º
-
+
N
N
-8
6
3
6+
8+
-7
4
5
0
60
50
40
32
33+
21
12
-12
2,6
2,2
1,8 0
1,2
1,0
0,8
0,6
0,2
1-7
?
1 2 3 4 5 67
ºC
110
+20
-20
Outside temperature in
º
C
Boiler water temperature or
flow temperature in ăC
º
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...