56
Control unit for constant temperature mode
Changing parameters in service positionsĂ"S
Ă
1" to "S
Ă
7"
(cont.)
S
Ă
3Ăć Max. boiler water temperature if DHW is heated
The display shows values in
º
C. As delivered condition:Ă"78".
For setting steps, see pageĂ54.
Control unit setting range 50 to 125Ă
º
C, limited by the thermostat to 84Ă
º
C.
To optimise control characteristics, only select boiler water temperatures up
to a maximum of 78Ă
º
C.
S
Ă
4Ăć Additional function for heating DHW
(for gas-fired boilers)
The DHW cylinder will briefly be heated by the additional function to 60Ă
º
C.
You can select the frequency.
For setting steps, see pageĂ54.
Parameter
Heating frequency
0 (as delivered condition)
Additional function inactive
1 to 30
ă1 Every time DHW is heated,
it will be heated to 60Ă
º
C
to
30 Every 30thĂDHW heating
it will be heated to 60Ă
º
C
S
Ă
5Ăć DHW heating
Different options for DHW heating may be selected.
For setting steps, see pageĂ54.
Parameter
Domestic hot water heating
0ăAs delivered condition ć gas-fired boiler no DHW heating
1
DHW cylinder temp. control
2
DHW cylinder temp. control
(optimised)
*1
3
N/A
4
N/A
5
N/A
6
N/A
*1
Automatic adjustment, if a DHW cylinder temperature sensor is connected; can be
manually changed to "1".
5692Ă485
G
B
Summary of Contents for Vitodens 200
Page 25: ...25 Initial start up inspection and maintenance 5692Ă485 GB ...
Page 96: ...96 Control unit for weather compensated mode with Comfortrol prog unit 5692Ă485 GB ...
Page 99: ...101 5692Ă485ĂGB ...
Page 105: ...109 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 107: ...111 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...
Page 109: ...113 Appendix Maint service Maint service Maint service Maint service 5692Ă485ĂGB ...