VD120 Series Inverter User Manual Parameter Description
-
103
-
F7 Keyboard and Display Function Group
F7-00
JOG / REV Key
Function Selection
0: Invalid
1: Operation panel command channel
switching with remote command channel
(terminal command channel or
communication command channel)
2: FWD/REV switching
3: Forward jog
4: Reverse jog
5: Rapid debugging
3
◎
JOG/REV keys for the multi-function key, can be set by the function code JOG/REV key functions.
This key can be used to switch in stop and running.
0: This key invalid
1: Operation panel command channel switching with remote command channel
Refer to the command source switching, namely panel command source switching with
communication command source. If current command source is keypad control, then the key function
is valid.
2: FWD/REV switching
The direction of frequency command is switched by JOG/REV key. The funtion is valid only in the
command source for the operation panel command channel.
3: Forward jog
Through the keypad JOG/REV key to realize forward jog.
4: Reverse jog
Through the keypad JOG/REV key to realize reverse jog.
5: Rapid debugging
Through the keypad JOG/REV key to switch to the rapid debug interface, the specific interface
content reference FF-05 parameter description.
F7-01
STOP / RESET Key
Function
0: STOP/RES key stop function is valid
only in keypad operation mode
1: STOP/RES key stop function all valid
in any operation mode
1
○
This parameter is used to set the function selection of STOP/RESET key.
Remark: the “RESET” is always valid for the reset function, regardless of the value of the parameter
settings.
F7-02
LED Running Display
Parameter 1
0000~0xFFFF
Bit00: Running frequency 1 (Hz)
Bit01: Setting frequency (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI input state
Bit08: DO output state
Bit09: AI1 voltage (V)
0x001F
○