VD120 Series Inverter User Manual Communication Protocol
-
161
-
Output current high Bit
xxH
Output current low Bit
xxH
Output power high Bit
xxH
Output power low Bit
xxH
CRCCHK low Bit
xxH
CRCCHK high Bit
xxH
END
T1-T2-T3-T4
9.6.2 Command Code: 06H (00000110), write one word
Such as: Put 1000 (2710H) (namely write-in setting frequency F0-10*100%) write to slave address
01H to the 1000H of the inverter (communication set value address). The frame structure description
as below:
RTU Master command information.
START
T1-T2-T3-T4
ADDR
01H
CMD
06H
Write data address high Bit
10H
Write data address low Bit
00H
Data content high Bit
27H
Data content low Bit
10H
CRCCHK low Bit
97H
CRCCHK high Bit
36H
END
T1-T2-T3-T4
RTU slave response information.
START
T1-T2-T3-T4
ADDR
01H
CMD
06H
Write data address high Bit
10H
Write data address low Bit
00H
Data content high Bit
27H
Data content low Bit
10H
CRCCHK low Bit
97H
CRCCHK high Bit
36H
END
T1-T2-T3-T4
9.6.3 Communication Format Error Check Method
Frame error check mode includes two part verification, Bit check of byte (odd/even verify) and CRC