VD120 Series Inverter User Manual Function Parameter Table
-
15
-
F0-05
Frequency
Source
Superposition
Selection
Unit’s digit: frequency source
selection
0: Main frequency source A
1: Main auxiliary operation result
(operational relationship is
determined by ten bits)
2: Main frequency source A switching
with auxiliary frequency source B
3: Main frequency source A switching
with main and auxiliary operation
result
Ten’s digit: frequency source main
and auxiliary operation relationship
0: Main + auxiliary
1: Main – auxiliary
2: Max value of the two
3: Min value of the two
0x00
○
F0-06
Auxiliary
Frequency
Source B
Range
Reference
Selection when
Superimposed
1: Relative to the max frequency
2: Relative to frequency source A
0
○
F0-07
Auxiliary
Frequency
Source B
Range when
Superimposed
0%~150%
100%
○
F0-08
Auxiliary
Frequency
Source B
Offset
Frequency
when
Superimposed
0.00Hz~max frequency F0-10
0.00Hz
○
F0-09
Digital Setting
Frequency
0.00Hz~max frequency (F0-10)
50.00Hz
○
F0-10
Max Frequency
50.00Hz~600.00Hz
50.00Hz
◎
F0-11
Frequency
Upper Limit
Source
0: F0-12 setting
1: AI1
2: Reserved
3: Reserved
4: PULSE setting
5: Communication setting
0
◎
F0-12
Frequency
Upper Limit
Frequency lower limit F0-14~max
frequency F0-10
50.00Hz
○