Function Parameter Table VD120 Series Inverter User Manual
-
38
-
Protection
Action
Selection 2
Ten’s digit: parameter read-write
abnormal (21)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: running time reached
(27)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: reserved
Ten thousand’s digit: reserved
F9-38
Fault
Protection
Action
Selection 3
Unit’s digit: user-defined fault 1 (35)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: user-defined fault 2 (36)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: power on time
reached (28)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: offload (37)
0: Coast to stop
1: Stop according to stop mode
2: Decelerate to 7% of the rated
motor frequency continue running,
automatically restored to the set
frequency operation when no offload
(Acceleration and deceleration time
is Fb-07 and Fb-08)
Ten thousand’s digit: PID feedback
lost when running (23)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
0x00000
○
F9-39
Fault
Protection
Action
Selection 4
Unit’s digit: Disconnection detection
fault (22)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: reserved
0x00000
○