Function Parameter Table VD120 Series Inverter User Manual
-
34
-
F8-27
Voltage
Judgment
Value Upon
Instantaneous
Power Failure
60.0%~100.0% (Standard bus
voltage)
80.0%
○
F8-28
Maximum
Change of V/F
Over Voltage
Stall
0: No limit
1~30000
800
○
F9 Fault Record and Setting
Function
Code
Parameter
Name
Setting Range
Factory
Default Value
Property
F9-00
Fault Types for
the First Time
-
●
F9-01
Fault Types for
the Second
Time
-
●
F9-02
Fault Types for
the Third Time
(Last Time)
0: No fault
1: Acceleration over current
(hardware)
2: Deceleration over current
(hardware)
3: Constant speed over current
(hardware)
4: Acceleration over current
(software)
5: Deceleration over current
(software)
6: Constant speed over current
(software)
7: Acceleration overvoltage
8: Deceleration overvoltage
9: Constant speed overvoltage
10: Under voltage
11: Motor overload
12: Inverter overload
13: Input phase loss
14: Output phase loss
15: Module overheat
16: Reserved
17: External fault
18: Communication abnormal
19: Current detection abnormal
20: Motor tune abnormal
21: EEPROM read-write fault
22: Disconnection detection fault
23: PID feedback lost at runtime
24: Motor short circuit to ground
-
●