Parameter Description VD120 Series Inverter User Manual
-
66
-
related parameters.
9: Communication setting
Refers to the main frequency source by the HC is given by way of communication.
VD120 support Modbus communication mode.
Modbus communication is standard, the other two kinds of communication card is optional, the user
to select according to need, and need to set the parameters F0-23 (communication extension card
type) correctly.
10: Keypad potentiometer
Frequency source is given by keypad potentiometer.
F0-03
Main Frequency
A Gain
0.000~10.000
1.000
○
The actual value of main frequency source A=F0-02*F0-03.
F0-04
Auxiliary Frequency
Source B Selection
Same as F0-02
(Main Frequency Source A Selection)
0
◎
Auxiliary frequency source as a separate frequency given channel (that is, the switching frequency
source selection for A to B), its usage same as the main frequency source A, the method of use can
reference the related description of F0-02.
When auxiliary frequency source used as superposition of given (i.e. frequency source selection for
A+B, A to A+B switch or B to A+B switch), need to pay attention to:
1)
When the auxiliary frequency source for digital given, preset frequency (F0-09) doesn’t work,
the user through the keyboard ▲,▼ key (or the UP/DOWN of multi-function input terminal) for
the adjustment of the frequency.
2)
When the auxiliary frequency source for analog input given (AI1, AI2) or pulse input given, input
100% of the set corresponding auxiliary frequency source range, can be set through by the
F0-06 and F0-07.
3)
When frequency source for pulse input given, is similar to analog given.
Tip: auxiliary frequency source selection B and main frequency source A selection, can’t be set to the
same channel, namely F0-02 and F0-04 can’t set to the same value, otherwise easy to cause
confusion.
F0-05
Frequency Source
Superposition
Selection
Unit’s digit: frequency source selection
0: Main frequency source A
1: Main auxiliary operation result (operational
relationship is determined by ten bits)
2: Main frequency source A switching with
auxiliary frequency source B
3: Main frequency source A switching with
main and auxiliary operation result
Ten’s digit: frequency source main and
auxiliary operation relationship
0: Main + auxiliary
1: Main – auxiliary
2: Max value of the two
3: Min value of the two
0x00
○
Through this parameter selection frequency given channel. Through the compound of main frequency
source A and auxiliary frequency source B to achieve frequency given.
Unit’s digit: frequency source selection