Parameter Description VD120 Series Inverter User Manual
-
100
-
33
PLC circulation output
When simple PLC operation to finished a cycle, output a pulse
signal whit 250ms width.
34
Frequency limit
When set frequency exceed frequency upper limit or
frequency lower limit, and the inverter output frequency
reaches frequency upper limit or frequency lower limit, output
ON signal.
35
Torque limit
Inverter in speed control mode, when output torque reaches
the torque limit value, the inverter in the stall protection state,
output ON signal at the same time time.
36
Reverse running
When frequency inverter in reverse running, output ON signal.
37
AI1 input limit
When the value of analog input AI1 is more than Fb-41 (AI1
input protection upper limit) or less than Fb-40 (AI1 input
protection lower limit), output ON signal.
39
Communication setting
Please refer to the communication protocol.
41
Timing braking (power
on braking)
Please refer to the instruction of function code Fb-48, Fb-49.
42
Inverter in running (jog
no output)
Said the inverter is in running state, have the output frequency
(can be zero), except jog, then output ON signal.
F6-06
DO Output Terminal
Effective State
Selection
Unit’s digit: HDO1
0: Positive logic
1: Anti-logic
Ten’s digit: RELAY1, same as above
0x00
○
Define the output logic of HDO1 and relay 1.
0: Positive logic, digital output terminal and the corresponding piplic end connected to valid state,
disconnect as invalid state;
1: Anti-logic, digital output terminal and the corresponding public end connected as the invalid state,
disconnect for valid state.
F6-07
HDO1 Closing Delay
0.0s~3600.0s
0.0s
○
F6-08
T1 Closing Delay
0.0s~3600.0s
0.0s
○
Set the closing delay time of output terminal HDO1 and relay 1, from the state to change to the actual
output changes.
F6-12
HDO1 Output Function
Selection
0
○
F6-13
AO1 Output Function
Selection
0~15, see table below
0
○
Analog output AO1 and AO2 output range is 0V~10V or 0/4mA~20mA. HDO1 terminal output pulse
frequency range is 0.01kHz~F6-15(output max frequency when HDO1 pulse output mode), F6-15
can be set from 0.01kHz~100.00kHz. Pulse or analog signal output 0.0%~100.0% corresponding
function as below table: