Parameter Description VD120 Series Inverter User Manual
-
64
-
Chapter 6 Parameter Description
F0 Basic Function
F0-00
Motor Control Mode
0: V/F control
1: SVC
0
◎
0: V/F control mode:
Suitable for load demand is not high, or a frequency inverter drive multi-motors application, such as
fan and pump load.
1: SVC
Refers to the open loop vector control, suitable for the usual higher performance control occasions,
one frequency inverter can only drive a motor. Such as machine tools, centrifuge, wire drawing
machine, injection machine and the load.
F0-01
Running Command
Source Selection
0: Control panel command source (L/R OFF)
1: Terminal command source
(L/R ON)
2:Communication command source (L/R
flashes)
0
○
Select inverter run command source:
Inverter run command include: start, stop, forward run, reverse run, jog, etc.
0: Control panel command source (L/R OFF)
Key” RUN, JOG/REV, STOP/RESET” on control panel to realize command control.
1: Terminal command source (L/R ON)
Through multi-function input terminal to realize command control.
2: Communication command source (L/R flashes)
Operation command as setup via HOST PC via communication mode, when select this option, default
is Modbus communication (standard).
F0-02
Main Frequency
Source A Selection
0: Digital setting(F0-09, UP/DOWN can be
modified, no memory when power failure)
1: Digital setting(F0-09, UP/DOWN can be
modified, memory when power failure)
2: AI1
3: Reserved
4: Reserved
5: PULSE setting
6: MS reference
7: Simple PLC
8: PID
9: Communication setting
10: Keypad potentiometer
10
◎
Select inverter input channel of in main given frequency, total 11 kinds of main given frequency
channel.
0: Digital setting(no memory when power failure)
Summary of Contents for VD120 Series