Parameter Description VD120 Series Inverter User Manual
-
106
-
Set frequency (Hz)
0x0001
Bus voltage (V)
0x0002
DI input state
0x0004
DO output state
0x0008
AI1 voltage (V)
0x0010
Reserved
0x0020
Reserved
0x0040
Count value
0x0080
Length value
0x0100
PLC stage
0x0200
Load speed
0x0400
PID setting
0x0800
PULSE input frequency (kHz)
0x1000
Setting torque (0.1%)
0x2000
If you want to show multiple parameters (switch by shift key display), only to input hexadecimal
addition results of that several parameter.
F7-05
The Second Line LED
Running Display
Parameters
0~15 corresponding bit0~bit15 of F7-02
16~31 corresponding bit0~bit15 of
F7-03
4
○
F7-06
The Second Line LED
Stop Display Parameters
0~13 corresponding bit0~bit13 of F7-05
1
○
When use the double line show keyboard, can select a display value by these two parameters, but the
function is the decimal input.
F7-07
Load Speed Display
Coefficient
0.0001~6.5000
1.0000
○
F7-08
Load Speed Display
Decimal Places
0: 0 bit decimal place
1: 1 bit decimal place
2: 2 bit decimal place
3: 3 bit decimal place
1
○
When need to display the load speed, should adjust the corresponding relation of inverter output
frequency and load speed.
Below illustrates the calculation of load speed:
If load speed display coefficient F7-07 is 2.000, the load speed decimal digits F7-08 to 2 (two decimal
point), when inverter running frequency for 40.00Hz, load speed is: 40.00*2.000=80.00 (two decimal
point display).
If the inverter in a stop state, the load speed display for set frequency corresponding to the speed,
namely “setting load speed”. At a set frequency of 50.00Hz for example, the stop state load speed is:
50.00*2.000=100.00 (two decimal point display).