Parameter Description VD120 Series Inverter User Manual
-
124
-
Fb-32
Any Current Reaching 2
Amplitude
0.0%~300.0% (rated motor current)
0.0%
○
When the output current of frequency converter is set at the positive and nagetive detection amplitude
of any current reaching, inverter muti-function the DO output ON signal.
VD120 provide two sets of any current reach and the detection amplitude parameter, the following
figure is the function diagram.
Output current
Any current reaching
Frequency detection range
Frequency detection range
Time
OFF
OFF
OFF
OFF
ON
ON
ON
Any frequency reaching
detection signal DO or
relay
Fig 6-28 Schematic diagram of any current reaching detection
Fb-33
The Running Reached
Time Setting
0.0Min~6500.0Min
0.0Min
○
When the start of the run time reached this time, the frequency converter multi-function digital DO
function output ON signal "current running time reached".
Fb-34
Accumulative Power-on
Reached Time Setting
0h~65000h
0h
○
Used to set the inverter power on time.
When the accumulative power on time (FF-15) reached the setting accumulative power on time,
frequency converter multi-function digital DO output ON signal.
Fb-35
Accumulative Running
Reached Time Setting
0h~65000h
0h
○
Used to set the inverter running time.
When the accumulative running time (FF-14) reached the setting accumulative running time, inverter
multi-function digital DO output ON signal.
Fb-36
Timing Function
Selection
0: Disabled
1: Enabled
0
○
Fb-37
Timed Running Time
Selection
0: Fb-38 setting
1: AI1
Analog input range corresponding to the
Fb-38
0
○
Fb-38
Timed Running Function
0.0Min~65000.0Min
0.0Min
○
This group of parameters used to complete the timing run function of the inverter.
When Fb-36 timing function selection is effective, the inverter timing starts when it is started, to set
timing run time, the inverter automatically stop, muti-function DO output ON signal at the same time.