Parameter Description VD120 Series Inverter User Manual
-
98
-
F6 Output Terminal Function Group
F6-00
DO1 Terminals Output
Mode Selection
0: HDO1 pulse output (optional)
1: Switch output
1
○
DO1 terminal is programmable multiplexing terminal. It can be used as high-speed pulse output
terminal, it can also be used as collector open circuit output terminal, high speed pulse output function
is optional, if you need this feature, you need to contact the manufacturer in advance.
When as a pulse output, the highest frequency of the output pulse is 100kHz, related functions refer
to the instruction of F6-12.
F6-01
DO1 Output Terminals
Function Selection
0
○
F6-02
Relay T1 Function
Selection
0~42, see table blow
0
○
Digit output terminal function table:
Set
Value
Function
Description
0
No output
Output terminals without any function.
1
Inverter in running
It indicate the inverter is in running state, have the output
frequency( can be zero), output ON signal at this time.
2
Ready for run
When the inverter main circuit and control loop is stable, and
the inverter is not detected any fault information, and the
inverter is in the running sate, output ON signal.
3
Fault output 1 (no
output when continue
to run )
When the inverter is failure (except when the fault protection
action is continue operation), output ON signal.
4
Fault output 2 (no
output undervoltage or
continue to run)
When the inverter is failure (except when undervoltage or fault
protection action is continue operation), output ON signal.
5
Warning output 3
(output when fault)
When the inverter is failure, output ON signal.
6
Output undervoltage
When the inverter is in undervoltage condition, output ON
signal.
7
Frequency level
detection FDT1 output
Please refer to the instruction of function code Fb-16, Fb-17.
8
Frequency level
detection FDT2 output
Please refer to the instruction of function code Fb-18, Fb-19.
9
Frequency reached
Please refer to the instruction of function code Fb-20.
10
Frequency 1 reached
output
Please refer to the instruction of function code Fb-21, Fb-22.
11
Frequency 2 reached
output
Please refer to the instruction of function code Fb-23, Fb-24.
12
Zero speed running 1
(no output when stop)
When frequency inverter is running and the output frequency
is 0, then output ON signal. When inverter is in a state of
downtime, the signal is OFF.